APC MGE Galaxy 3500 30kVA 400V 3:1 with 3 Battery Modules Expandable to 4 (G35T30K3I3B4S)

    Buy APC MGE Galaxy 3500 30kVA 400V 3:1 with 3 Battery Modules Expandable to 4 (G35T30K3I3B4S)

    30kVA 400V 3:1 with 3 Battery Modules Expandable to 4, Start-up 5X8 | 10-40kVA compact 3 phase UPS | 24.0kWatts / 30.0kVA
    Rp 181,000,000
    • Faster delivery
      We offer domestic and international shipping via all major shipping carriers.
    • Secure payment
      We accept all major credit cards and PayPal payments. All orders are paid online.
    • Contact us
      If you are in Surabaya, Indonesia, you may pick up an order in one of our stores. Give us a call!
    SKUC3MA010080
    Voltase Keluar230V
    Voltase Masuk400V 3PH
    Garansi produk1 Tahun
    BrandAPC
    Spesifikasi
      Output
    • Output power capacity : 24.0kWatts / 30.0kVA
    • Output Voltage Note : Configurable for 220 : 230 or 240 nominal output voltage
    • Efficiency at Full Load : 95.8 %
    • Output Voltage Distortion : Less than 5% Output Frequency (sync to mains) : 47 - 53 Hz for 50 Hz nominal
    • Output Frequency (not synced) : 50Hz +/- 0.1% for 50Hz nominal
    • Other Output Voltages : 220, 240
    • Load Crest Factor : Unlimited
    • Topology : Double Conversion Online
    • Waveform type : Sine wave
    • Overload Operation : 10 minutes @ 125% and 60 seconds @ 150%
    • Output Connections : (1) Hard Wire 3-wire (H N + G) (Battery Backup)
      Input
    • Input frequency : 40 - 70 Hz (auto sensing)
    • Input Connections : Hard Wire 5-wire (3PH + N + G)
    • Input voltage range for main operations : 304 - 477V
    • Input voltage adjustable range for mains operation : 340 - 460 (400V)V
    • Efficiency at Full Load : 95.8 %
    • Input Total Harmonic Distortion : Less than 5% for full load
    • Type of Input Protection Required : 3-pole breaker
    • Other Input Voltages : 380, 415
    • Maximum Input Current : 41.0A
    • Input Power Factor at Full Load : 0.98
    Antarmuka / InterfaceDB-9 RS-232
    Baterai
    • Battery Type : Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
    • Included Battery Modules : 3
    • Battery Slots Empty : 1
    • Typical recharge time : 5 hour(s)
    • RBC Quantity : 3
    • Nominal Battery Voltage : +/-192 V (split battery referenced to neutral)
    • End of Discharge Battery Voltage : +/-154 V
    • Efficiency in Battery Operation : 95.00 %
    • End of Discharge Maximum Battery Current : 109 A
    • Overload Operation : 10 minutes @ 125% and 60 seconds @ 150%
    Loading